    General 

    SHUANGFENG® Electrical strives to bring our customers the latest technology and competitive pricing and best service for distribution automatic.
    SFS is an SF6-insulated, outdoor pole mounted load break switch family for overhead lines and specifically
    designed for use in modern remote controlled distribution automation systems. The SFS offers reliable maintenance  free operation even in the most demanding climatic conditions including salt laden atmospheres, corrosive industrial
    pollution, snow and ice. It has excellent load breaking and fault making capacity and satisfies the isolation
    requirements specified for load break switch. The earthed metal tank prevents all possible leakage currents across an open switch. RPS can be manually operated or motor operated for local and remote electric control, upgraded.

    Service environment

    1.Air temperature: Maximum temperature: +85℃; Minimum temperature:-45℃
    Humidity: Monthly average humidity 95%; Daily average humidity 90% .
    Altitude above sea level: Maximum installation altitude: 2500m or more higher.
    Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. No frequent violent shake 

    Offering

    With optional classes for rated current range:--Type SFS 15, Rating6-20 kV with 400A, 16 kA up to 1250A, 20kA;--Type SFS 27, Rating22-27 kV with 400A, 16 kA up to 1250A, 20kA;--Type SFS 38, Rating30-40.5 kV with 400A, 16 kA up to 1250A, 20kA;With optional classes for different grid application installation:Section function (Section)50 Instantaneous/Definite-Time Overcurrent(P.OC)51 Phase Time-Overcurrent(P.Fast curve/P.Delay curve)Overload (N.Fast curve/N.Delay curve)50N Residual Ground Instantaneous/Definite-Time Overcurrent(G.OC)51N Residual Ground Time-Overcurrent (G.Fast curve/G.Delay curve)50SEF Sensitive Earth Fault (SEF)51c Cold Load(Cold load)TRSOTF Switch-Onto-Fault(SOTF)59 Over Voltage(L.Over volt)27 Under Voltage (L.Under volt)


    656afb00ur

    Monitoring Functions:Primary/Secondary Phases and Earth CurrentsDirectionPrimary/Secondary Line and Phase VoltagesApparent Power and Power FactorReal and Reactive PowerHistorical Demand RecordPositive Phase Sequence Voltage & CurrentNegative Phase Sequence Voltage & CurrentZero Phase Sequence VoltageFrequencyBinary Input/Output statusTrip circuit healthy/failureTime and dateFault recordsEvent records


    Time-Overcurrent Curves

    IEC Curves:C1 (Standard Inverse)C2 (Very Inverse)C3 (Extremely Inverse)C4 (Long-Time Inverse)C5 (Short-Time Inverse)

    656afba3jm

    U.S. Curves: U1 (Moderately Inverse) U2 (Inverse) U3 (Very Inverse) U4 (Extremely Inverse) 

    656afbfc9g

    PC software for controller Testing, Setting, programing, Update.

    nhgfjuytumukjhgfjhgfyuytul24jghfjhgfjhgfuoy

    SFS feature

    The high quality 3 mm stainless steel are used for tank, which is designed for its maximum robustness and minimum welding line to minimize corrosion, and specifically to guarantee the safety of the
    operation personnel even with the internal arc faults at the maximum fault capacity of the tank the SFS can withstands an internal fault without venting hot gases.
    The independent spring operation mechanism adopt SHUANGFENG® patent spiral spring, provides a guaranteed load break fault make capability by ensuring the opening and closing speed of the switch.
    The SFS is provided with light reflecting position indicator which are directly connected to the switch operating
    shaft providing clear and unambiguous switch position indication. Indicator made of light reflecting material, which is easily visible from ground level even at night in driving rain.

    Main new advantages of SFS

    SHUANGFENG® Supply special design manual closing device technology with own patent, It applied for normal and abnormal situation closing. It’s closing speed(time) comply with IEC62271-100.
    This function can offset from magnetic actuator fault which when actuator can’t work will cause the major accident.

    Corrosion resistant, Composite bushingManual lock-out mechanism (including hook stick)Reliable housing groundO/C indicator (made of light reflecting material),Operation counter, Gas density gauge which are easilyvisible from ground level.Advanced and Integrated helium leakage detectingand filling equipment, which ensuring SF6 leakage ofeach switch is less than 0.1% strictly per year.Motor drive, which easily retrofitted on site tomanually operated units.

    656afceysl

    Creepage Distances of SFS

    Terminal to ground creepage 15kV BIL 95/110kV 27kV BIL125/150kV 38kV BIL 170/200kV
    Composite bushing 564mm 840mm 1400mm
    Porcelain bushing 556mm 708mm 1250mm

    Current transformer and Voltage sensor

    Part Number SFS-15 SFS-27 SFS-38
    Manual Motorize Manual Motorize Manual Motorize
    Current transformer / 3 / 3 / 3
    Voltage sensor / 3/6 / 3/6 / 3/6

    Standards for reference

    LAC18g

    Main technical data

    Insulation level
    Rated voltage kV 15 27 38
    Power frequency withstand voltage, 50 Hz
    - to earth and between phases kV 28 50 70
    - across the isolating distance kV 32 60 80
    Lightning impulse withstand voltage
    - to earth and between phases kV 75 125 170
    - across the isolating distance kV 85 145 195
    Current ratings
    Rated normal current A 400/630/800/1250
    Mainly active load breaking current A 400/630/800/1250
    Number of breaking operations CO times 400
    Line-charging breaking current A 50 50 2
    Cable-charging breaking current A 50 50 40
    Earth fault breaking current A 50 50 130
    Cable charging breaking current        
    under earth fault conditions A 28 28 80
    No-load transformer breaking current A     20
    Short-circuit ratings
    Short-time withstand current, Ik kA/s 20 kA/4 s 20 kA/4 s 20 kA/4 s
    Peak withstand current kA 50 50 50
    Short-circuit making current kA 50 50 50
    Number of making operations
    - main switch 50 kA (CLE3) times 5 5 5
    - main switch 31.5 kA (CLE3) times 10 10 10
    - earthing switch 50 kA (CLE2) times 3 3 3
    - earthing switch 31.5 kA (CLE3) times 5 5 5
    Ambient air temperature limits   -40°C...+60°C
    Mechanical endurance (number of CO operations)
    - main switch times 5000 5000 5000
    - earthing switch times 2000 2000 2000
    Filling pressure (+20°C) bar (abs) 1.4-1.5 1.4-1.5 1.8-1.9
    Alarm pressure (+20°C)
    - density switch bar (abs) 1.2 1.2 1.65
    - density gauge bar (abs) 1.2 1.2 1.6
    - low gas lock-out mechanism bar (abs) 1.1 1.1 1.6
    Weight
    Composite bushing kg 115 125 135
    Porcelain bushing kg 125 135 155
    Motorize   Add 20kg
    Degree of protection of the mechanism box   IP67

    Mobile APP software GPRS/GSM/WIFI/BLUETOOTH

    7VHtao

    Master software for Distribution Automation Management

    HFGDUYjx0

    Outline & Sizes for SFS

    hjkhe67