33Kv 35Kv 36Kv 38Kv 40.5Kv Distribution Pole Mounted Vacuum Recloser SFE 3 Phase Vacuum Auto Recloser Circuit Breaker
SFE
Pole mounted vacuum Recloser 33kV,….40.5kV,630A,..1250A

Signal words
The signal words "danger," "warning" and "caution" used in this manual indicate the degreeof hazard that may be encountered by the user. These words are defined as:
Danger - Indicates an imminently hazardous situation that, if not avoided,will result in death or serious injury.
Warning - Indicates a potentially hazardous situation that, if not avoided,could result in death or serious injury.
Caution - Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury.
Caution (without safety alert symbol) -Indicates a potentially hazardous situation that, ifnot avoided, may result in property damage.
Field service operation and warranty issues:
SHUANGFENG can provide competent, well trained field service representatives to provide technical guidanceand advisory assistance for the installation, overhaul, repair and maintenance of SHUANGFENG equipment,processes and systems.
1. Summary
With the rapid development of computer technology, transducer technology, and network
communication, the power system network has advanced requirements. As a result, using primary equipment with single functionality has become inconvenient. To address this issue, it is necessary to develop intelligent integration switches based on terminals for the entire power system. Our
company has developed the SFE Series, an intelligent integration outdoor AC high voltage vacuum circuit recloser, which is an upgrade from outdoor vacuum circuit breakers. Our reclosers comply with relevant standards, making them a reliable choice.
ANSI/IEEE C37.60/IEC 62271-111( GB1984-2003 China standard)
GBT11022-1999 China Standard
IEC 60255-11
IEC 60255-21-1 Class I
IEC 60255-21-2 Class I
IEC 60255-21-3 Class I
IEC 60255-22- 1 Class III
IEC 60255-22-2 Class IV
IEC 60255-22-3 Class III
IEC 60255-22-4 Class IV
IEC 60255-22-5
IEC 60255-22-6
IEC 60255-25
IEC 60255-5
IEC 62271-1
2. Using condition
Ambient temperature: -40℃~+85℃, day temperature difference: 25℃;
Altitude:≤3000m area;
Wind speed no exceeds 35m/s;
No normally intensity vibration
No intensity erosion gas, medium place (for example acid, alkali, smother eg.)
Pollution class: IV class;
Charge temperature -40℃~+85℃。
3. Before using reminding
To ensure the highest level of quality and performance, the SFE Series switch undergoes thorough factory adjustment and sealing. Additionally, we provide a cable connector assembly that allows for easy interconnection of wiring to the SFE switch. For added flexibility, we also offer optional accessories such as potential transformers or surge arresters that can be supplied with the switch.
Optional accessories list
|
Products name and type |
Purpose |
Picture for reference |
||
|
Potential transformer |
Standard |
The secondary output voltage for electronic controller's auxiliary power supply is customized to meet customer requirements, with a burden range of 50VA to 500VA. PT can be either oil- immersed or dry-type. |
|
|
|
11/0.22kV |
||||
|
11/0.11kV |
||||
|
22/0.22kV |
||||
|
22/0.11kV |
||||
|
330.22kV |
||||
|
33/0.11kV |
||||
|
(Lightning arrester) |
Surge arrester |
Standard |
For over voltage release protection, Details is according to clients’ requied |
|
|
SFA-11L |
||||
|
SFA-15L |
||||
|
SFA-24L |
||||
|
SFA-30L |
||||
|
SFA-33L |
||||
|
SFA-36L |
||||
|
Special HV Voltage sensor |
For 3 phase voltage measuring |
Inside of circuit breaker |
||
Note:
As a required, Above equipment will be prepared by end-user.
Equipment Included with Each Recloser Set
|
Three Phase SFE circuit breaker unit with 1 pcs Electronic controller H42 type |
|||
|
|
|
|
|
|
Hardware provision to connect ground |
Provided and visible |
||
|
Cable Assembly,26 pins cable, standard 6M |
Provided and visible |
||
|
Manual Trip Lever |
Provided and visible |
||
|
Rubber Insulation cap |
Provided and visible |
||
4. Transport, Lifting, flitting notice
|
|
|
Make sure follow below item to Flitting the Recloser switch and storage, and mounting. |
4.1 Lifting of packing case
4.2 Transport
During transportation, the SFE circuit breaker is securely packed in a seaworthy manner and
positioned in the "OPEN" state. The circuit breaker is usually packed in one case with the
electronic control cabinet, while the steel support fittings and other accessories are packed in a separate case. The following documents are also included with the SFE breaker: instruction
manual, factory test certificates, drawings, and a packing list.
It is important to transport the circuit breakers only in their packed condition, taking necessary precautions to ensure safe and damage-free transportation.
. Ensure that packing cases are not placed on wet surfaces / waterlogged areas.
. Breakers should not be stacked one over the other.
4.3 Receipt & Storage prior to installation
Store the breaker indoors with complete packing to protect it from direct sunlight, rain, or snow.
The breaker can be stored for up to 3 months from the date of shipment from the factory. For longer storage, remove the packing and store the breaker in a controlled environment with a leakproof roof, solid and flat ground, relative humidity below 50%, and temperature of 20°C (±10°C).
4.4 Lifting of SFE circuit breaker

Note:
Very dangerous! Don’t allow to give much force on the bushing current transformer side.
5. S F E type Circuit Breaker unit installation on pole
Different sizes of mounting bracket
|
Type of SFE circuit breaker |
Sizes of mounting bracket notice |
|
SFE12, SFE15,GTE27 |
Phase distance 360mm |
|
SFE27H, GTE38 |
Phase distance 460mm or 560mm |
The weight of SFE12 circuit breaker =92kg. SFE15>E27=137kg.
SFE27H&SFE38 circuit breaker weight=300Fg.
6. GTK type Electronic controller installation on pole
GTK type electronic controller weight=20kg
Note:
The controller mounting bracket is provided by end-user. Above installation
Dimension for clients make controller’s mounting bracket using.
7. Interconnect with circuit breaker and electronic controller
7.1 GTE circuit breaker side defination
26 pins connector hole H
Note:
H type cable connector is prepared for 26 pins control cable to connect to electronic controller.
. With 3 phase current signals
. ON/OFF auxiliary signals
. OPEN/CLOSE coils wires.
7.2 CH-42 type electronic controller side cable defination
Main cable 10pins and 6 pins connect to SFE circuit breaker unit.
Plastic connector is prepared for PT auxiliary power incoming and RTU connection.
Note:
Both of the CH-42 circuit and controller has the grounding M12 bolt, Pls link it to earth suitable.