HY5(10)W-12 HY5(10)W-12J Surge Arrester
Description
Main features
|
Electrical characteristics |
Specification |
Unit |
|
|
Rated voltage of Surge arrreser |
12 |
kV |
|
|
Nominal discharge current |
5 |
10 |
kA |
|
Rated frequency |
50 |
Hz |
|
|
Maximum continuous operating voltage |
10.2 |
kV |
|
|
Steep current impulse residual voltage |
42.2 |
kV(Crest) |
|
|
Lightning Impulse residual voltage |
36 |
kV(Crest) |
|
|
Switching Impulse residual voltage |
31.7 |
kV(Crest) |
|
|
Long duration current impulse withstand voltage |
150 |
250 |
A |
|
High current impulses |
65 |
100 |
kA (Crest) |
|
Rated Short-circuit current |
20/12/6/ 0.6 ± 0.2 |
kA |
|
|
Class of Surge arrester |
Class 1 or Class 2 |
||
|
Application |
Distribution type |
||
|
With or without gap |
Gapless |
||
|
Designation of arrester |
Design B |
||
|
Spare parts |
|||
|
NEMA A or B mounting bracket |
with/without |
||
|
Disconnector |
with/without |
||
|
Earth lead |
with/without |
||
|
Bird guard cap |
with/without |
||
|
Line clamp |
with/without |
||
|
Upper terminal (incoming line) bolt size |
M12 |
||
|
Lower termina (outgoing line) bolt size |
M10 |
||
|
Material |
|||
|
Upper terminal |
Stainless steel 304 |
||
|
Housing |
Polymer type |
||
|
Color of housing |
Dark grey / light grey |
||
|
Varistor |
High quality zinc oxide varistor |
||
|
Size of Varistor |
35mm / 38mm /40mm / 42mm |
||
|
Package |
|||
|
Qty/package |
3 |
pc/carton |
|
|
Service conditions |
|||
|
Environment maximum temperature |
40 |
℃ |
|
|
Pollution level |
Heavy |
||
|
Altitude |
1000 |
Meter |
|
|
Standard |
IEC60099-4:2014 |
||