FSC-30 Outdoor high-voltage Drop Out Fuse Cutout

Characteristic:

Voltage: 24~27kV

Current: 100A/200A/300A

Creepage: 620mm/520mm

Standard: IEC60282-2

Main features

    FSC-30 Drop Out Fuse Cutout

    FSC series drop out cutout with standard fuse link protects the transformer, capacitors, cables or lines from the short circuit and over load in 11KV~38KV overhead distribution systems. Dropout Fuse Cutout is a kind of outdoor used high voltage protective device.To be connected with incoming feeder of distribution transformer or distribution line it mainly protect transformer or lines from short circuit and overload,and on/off loading current.

    Dropout Fuse Cutout is composed of insulator supports and fuse tube,static contacts is fixed on two sides of insulator support and moving contact is installed on two ends of fuse tube.Fuse tube is composed of inside extinguishing tube,outer phenol compound paper tube or epoxy glass tube.Load switching fuse cutout provides enforced elastic auxiliary contacts and arc-extinguishing enclosure for switching on/offloading current.At normally working via fuse link tightened the fuse tube is fixed to form up of close position.In case system occur faults,fault current result in fuse melt immediately and take place electric arc,which let arc-extinguishing tube being heated and explode a lot of gas.This will produce high pressure and blow off the arc along with tube.

    After fuse link melt moving contact has no tightened strength again,mechanism is locked and fuse tube dropout.Cutout now is in open position.

    When it needs to switch off during cut out loading.Operator shall via insulating operating bar pull the moving contact,at its beginning main contact and auxiliary static contact is contacted still.

    Whiling pulling the auxiliary contact is separated between auxiliary contacts there occur electric arc and the arc will be lengthened in arc-extinguishing enclosure gap and meanwhile arc-extinguishing explode gas to blow off the arc during current passing zero.

    Characteristic:

    Voltage: 24~27kV

    Current: 100A/200A/300A

    Creepage: 620mm/520mm

    Standard: IEC60282-2

    Main features

    Technical parameter.

    Electrical characteristics

    Specification

    Unit

    Voltage

    24~27

    KV

    Current

    100/200/300

    A

    Frequency

    50/60

    Hz

    Power frequency withstand voltage to earth (1 min)

    50

    KV

    Power frequency withstand voltage phase to phase (1 min)

    60

    KV

    Impulse voltage to earth

    150

    KV

    Impulse voltage phase to phase

    160

    KV

    Breaking current

    8

    KA

    Creepage distance:

    620/520

    mm

     

     

     

    Spare parts

     

     

    Mounting bracket

    with/without

     

    Arc shortening rod

    with/without

     

    Arc distinguish chamber

    with/without

     

    Fuse link

    without

     

     

     

     

     

     

     

    Material

     

     

    Copper content for brass

    Brass (60~62%)

     

    Conductive parts material

    Copper with silver plated/Copper with tin plate

     

    Insulator

    Porcelain/Polymer

     

    Fuse tube

    Fiber glass

     

     

     

     

    Package

     

     

    Qty/package

    1

    pc/carton

     

     

     

    Service conditions

     

     

    Environment maximum temperature

    40

    Pollution level

    II

     

    Altitude

    ≤1000

    Meter

     

     

     

    Standard

    IEC60282-2

     

     

    Fuse cutout structure

    Main bearing structure and main bearing structure

    IMG_256

    Fuse cutout accessories

    Including lower general bearing of fuse, arc extinguishing housing, American type fusible load with knife and 300A fusible load