Factory price 11kV 12kV 15kV SF6 Air Insulated Pole Load Break Switch Load Breaking Switches

SF6 sectionalizer/load breaker, suitable for 12/24/36 kV, 630A, 50/60Hz power grids, handles circuit opening, load current closing, system overload currents and automatically isolates faulty distribution lines; it uses the latest technology with a new electronic controller (housed in a weather-resistant stainless steel cabinet with wired/wireless modems for remote monitoring/control), supports manual, electric and remote operation, and features easy, fast pole-mounted installation to cut construction costs.

    Main image:

    SFS-1 Pole-mounted SF6 Load Breaker Switch-1.png

    Three-view drawing:

    SFS

    Pole mounted SF6 Load break switch Manual/Motorize

    6kV,….40.5kV, 400A,..630,….1250A

    Provided Customized manufacture

    Whole solutions for design, assembly, test …

    Catalog

    Summary

    SHUANGFENG Electrical strives to bring our customers the latest technology and competitive pricing and best service for distribution automatic.

    SFS is an SF6-insulated, outdoor pole mounted load break switch family for overhead lines and specifically

    designed for use in modern remote controlled distribution automation systems. The SFS offers reliable maintenance free operation even in the most demanding climatic conditions including salt laden atmospheres, corrosive industrial

    pollution, snow and ice. It has excellent load breaking and fault making capacity and satisfies the isolation

    requirements specified for load break switch. The earthed metal tank prevents all possible leakage currents across an open switch. RPS can be manually operated or motor operated for local and remote electric control, upgraded.

    Service environment

    1.Air temperature: Maximum temperature: +85℃; Minimum temperature:-45℃

    Humidity: Monthly average humidity 95%; Daily average humidity 90% .

    Altitude above sea level: Maximum installation altitude: 2500m or more higher.

    Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. No frequent violent shake ● Offering

    With optional classes for rated current range:

    --Type SFS 15, Rating6-20 kV with 400A, 16 kA up to 1250A, 20kA;

    --Type SFS 27, Rating22-27 kV with 400A, 16 kA up to 1250A, 20kA;

    --Type SFS 38, Rating30-40.5 kV with 400A, 16 kA up to 1250A, 20kA;

    With optional classes for different grid application installation:

    Section function (Section)

    50 Instantaneous/Definite-Time Overcurrent(P.OC)

    51 Phase Time-Overcurrent(P.Fast curve/P.Delay curve)

    Overload (N.Fast curve/N.Delay curve)

    50N Residual Ground Instantaneous/Definite-Time Overcurrent(G.OC)

    51N Residual Ground Time-Overcurrent (G.Fast curve/G.Delay curve)

    50SEF Sensitive Earth Fault (SEF)

    51c Cold Load(Cold load)

    TRSOTF Switch-Onto-Fault(SOTF)

    59 Over Voltage(L.Over volt)

    27 Under Voltage (L.Under volt)

    Monitoring Functions:

    Primary/Secondary Phases and Earth Currents

    Direction

    Primary/Secondary Line and Phase Voltages

    Apparent Power and Power Factor

    Real and Reactive Power

    Historical Demand Record

    Positive Phase Sequence Voltage & Current

    Negative Phase Sequence Voltage & Current

    Zero Phase Sequence Voltage

    Frequency

    Binary Input/Output status

    Trip circuit healthy/failure

    Time and date

    Fault records

    Event records

    SFS-2.png

    Creepage Distances of SFS

    Terminal to ground creepage

    15kV BIL 95/110kV

    27kV BIL125/150kV

    38kV BIL 170/200kV

    Composite bushing

    564mm

    840mm

    1400mm

    Porcelain bushing

    556mm

    708mm

    1250mm

    Current transformer and Voltage sensor

    Part Number

    SFS-15

    SFS-27

    SFS-38

    Manual

    Motorize

    Manual

    Motorize

    Manual

    Motorize

    Current transformer

    /

    3

    /

    3

    /

    3

    Voltage sensor

    /

    3/6

    /

    3/6

    /

    3/6

    Note: Current transformers and voltage sensors can be customized according to requirements.

    Standards for reference

    IEC 62271-1 IEC 62271-102 IEC 62271-103

    High-voltage switchgear and controlgear. Part 103: switches for rated voltage above 1 kV up to and including 52 kV

    Front: Color clear O/C indicator Rear:Highly reliable explosion-proof valve,

    Inflatable/deflation integrated device

    Main technical data

    Insulation level

    Rated voltage

    kV

    15

    27

    38

    Power frequency withstand voltage, 50 Hz

    - to earth and between phases

    kV

    28

    50

    70

    - across the isolating distance

    kV

    32

    60

    80

    Lightning impulse withstand voltage

    - to earth and between phases

    kV

    75

    125

    170

    - across the isolating distance

    kV

    85

    145

    195

    Current ratings

    Rated normal current

    A

    400/630/800/1250

    Mainly active load breaking current

    A

    400/630/800/1250

    Number of breaking operations CO

    times

    400

    Line-charging breaking current

    A

    50

    50

    2

    Cable-charging breaking current

    A

    50

    50

    40

    Earth fault breaking current

    A

    50

    50

    130

    Cable charging breaking current

    under earth fault conditions

    A

    28

    28

    80

    No-load transformer breaking current

    A

    20

    Short-circuit ratings

    Short-time withstand current, Ik

    kA/s

    20 kA/4 s

    20 kA/4 s

    20 kA/4 s

    Peak withstand current

    kA

    50

    50

    50

    Short-circuit making current

    kA

    50

    50

    50

    Number of making operations

    - main switch 50 kA (CLE3)

    times

    5

    5

    5

    - main switch 31.5 kA (CLE3)

    times

    10

    10

    10

    - earthing switch 50 kA (CLE2)

    times

    3

    3

    3

    - earthing switch 31.5 kA (CLE3)

    times

    5

    5

    5

    Ambient air temperature limits

    -40°C...+60°C

    Mechanical endurance (number of CO operations)

    - main switch

    times

    5000

    5000

    5000

    - earthing switch

    times

    2000

    2000

    2000

    Filling pressure (+20°C)

    bar (abs)

    1.4-1.5

    1.4-1.5

    1.8-1.9

    Alarm pressure (+20°C)

    - density switch

    bar (abs)

    1.2

    1.2

    1.65

    - density gauge

    bar (abs)

    1.2

    1.2

    1.6

    - low gas lock-out mechanism

    bar (abs)

    1.1

    1.1

    1.6

    Weight

    Composite bushing

    kg

    115

    125

    135

    Porcelain bushing

    kg

    125

    135

    155

    Motorize

    Add 20kg

    Degree of protection of the mechanism box

    IP67