Signal words
The signal words "danger," "warning" and "caution" used in this manual indicate the degreeof hazard that may be encountered by the user. These words are defined as:
Danger - Indicates an imminently hazardous situation that, if not avoided,will result in death or serious injury.
Warning - Indicates a potentially hazardous situation that, if not avoided,could result in death or serious injury.
Caution - Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury.
Caution (without safety alert symbol) -Indicates a potentially hazardous situation that, ifnot avoided, may result in property damage.
Field service operation and warranty issues:
SHUANGFENG can provide competent, well trained field service representatives to provide technical
guidanceand advisory assistance for the installation, overhaul, repair and maintenance of SHUANGFENG
equipment,processes and systems.
Summary
With the rapid development of computer technology, transducer technology, and network
communication, the power system network has advanced requirements. As a result, using primary equipment with single functionality has become inconvenient. To address this issue, it is necessary to develop intelligent integration switches based on terminals for the entire power system. Our
company has developed the SFE Series, an intelligent integration outdoor AC high voltage vacuum circuit recloser, which is an upgrade from outdoor vacuum circuit breakers. Our reclosers comply with relevant standards, making them a reliable choice.
ANSI/IEEE C37.60/IEC 62271-111( GB1984-2003 China standard)
GBT11022-1999 China Standard
IEC 60255-11
IEC 60255-21-1 Class I
IEC 60255-21-2 Class I
IEC 60255-21-3 Class I
IEC 60255-22- 1 Class III
IEC 60255-22-2 Class IV
IEC 60255-22-3 Class III
IEC 60255-22-4 Class IV
IEC 60255-22-5
IEC 60255-22-6
IEC 60255-25
IEC 62271-1
IEC 60255-5
Using condition
Ambient temperature: -40℃~+85℃, day temperature difference: 25℃;
Altitude:≤3000m area;
Wind speed no exceeds 35m/s;
No normally intensity vibration
No intensity erosion gas, medium place (for example acid, alkali, smother eg.)
Pollution class: IV class;
Charge temperature -40℃~+85℃。
Transport, Lifting, flitting notice
4.2 Transport
During transportation, the SFE circuit breaker is securely packed in a seaworthy manner and
positioned in the "OPEN" state. The circuit breaker is usually packed in one case with the
electronic control cabinet, while the steel support fittings and other accessories are packed in a separate case. The following documents are also included with the SFE breaker: instruction
manual, factory test certificates, drawings, and a packing list.
It is important to transport the circuit breakers only in their packed condition, taking necessary precautions to ensure safe and damage-free transportation.
. Ensure that packing cases are not placed on wet surfaces / waterlogged areas.
. Breakers should not be stacked one over the other.
4.3 Receipt & Storage prior to installation
Store the breaker indoors with complete packing to protect it from direct sunlight, rain, or snow.
The breaker can be stored for up to 3 months from the date of shipment from the factory. For longer storage, remove the packing and store the breaker in a controlled environment with a leakproof roof, solid and flat ground, relative humidity below 50%, and temperature of 20°C (±10°C).
Lifting of SFE circuit breaker

Note:
Very dangerous! Don’t allow to give much force on the bushing current transformer side.
SFE type Circuit Breaker unit installation on pole

Different sizes of mounting bracket
| Type of SFE circuit breaker |
Sizes of mounting bracket notice |
| SFE12, SFE15,GTE27 |
Phase distance 360mm |
| SFE27H, GTE38 |
Phase distance 460mm or 560mm |
GTK type Electronic controller installation on pole
GTK type electronic controller weight=20kg
Note:
The controller mounting bracket is provided by end-user. Above installation
Dimension for clients make controller’s mounting bracket using.
Interconnect with circuit breaker and electronic controller
GTE circuit breaker side defination
Note:
H type cable connector is prepared for 26 pins control cable to connect to electronic controller.
. With 3 phase current signals
. ON/OFF auxiliary signals
. OPEN/CLOSE coils wires.
7.2 CH-42 type electronic controller side cable defination
Main cable 10pins and 6 pins connect to SFE circuit breaker unit.
Plastic connector is prepared for PT auxiliary power incoming and RTU connection.
Note:
Both of the CH-42 circuit and controller has the grounding M12 bolt, Pls link it to earth suitable.
Wiring principle of recloser

Note:
Power supply PT rated voltage is according to HV side rated voltage and LV side controllerusing. Standard Low voltage side requirement is 220Vac, 500VA.
Special requirement PLS consult with SHUANGFENG Electrical.
Normal operating for SFE recloser